Requirements for the Maximum Travel Distance to an Exit as provided in PD1185 FIre Code of the Philippines ([Rule III Sec. 3.4-3.16). .
Without automatic fire suppression system - 46 meters
With automatic fire suppression system - 61 meters
Exemptions:
Educational Occupancy
Child Day Care Centers
(a) ≤ 30.5 m (any room or intended as exit access)
(b) ≤ 45.8 m (any point in a room)
(c) ≤ 15.25 m (any point in a sleeping room)
(d) travel distance in (a) and (b) may be increased by 15.25 m when equipped with automatic fire suppression system
Institutional Occupancy
Hospital, Nursing Homes and Residential Custodial Care
(a) ≤ 30 m (any room or intended as exit access
(b) ≤ 46 m (any point in a room)
(c) ≤ 15 m (any point in a sleeping room)
(d) travel distance in (a) and (b) may be increased by 15 m when equipped with automatic fire suppression system
Residential Occupancy
Hotels – Maximum 30 m
Apartment Buildings – Maximum of 31 m from entrance door or 46.5 m when protected by automatic suppression system
Dormitories – Maximum of 30.48 m or 46 m when protected by automatic suppression system
Special Purpose Industrial Occupancy and Storage Occupancy
Maximum of 23 m
Business Occupancy
Maximum of 91.5 m when protected by automatic suppression system
Mercantile Occupancy
Maximum of 30.5 m or 46 m when protected by automatic suppression system
Total Pageviews
2540740
ATLAS-CPED
Archl Projects
Bidvertiser
Atlas-CPED
Thursday, February 19, 2009
PD 1185 Maximum Travel Distance to an Exit
Subscribe to:
Post Comments (Atom)
Random Posts
- 10.07.2012 - 0 CommentsReview classes for the January 2013 Architecture Board exam will start July 30, 2012 at the UAP Center…
- 07.02.2011 - 2 Comments1.0 BENEDICT BAUTISTA BAUTISTA UNIVERSITY OF THE PHILIPPINES-DILIMAN 86.202.0 EMMELINE ABUGAN CO MAPUA…
- 19.01.2015 - 0 CommentsThe newest addition to the series of Architecture Board Exam Reviewers. Here's a Quiz based on Cyril M.…
- 11.09.2009 - 1 CommentsPart 1 of Tropical Design Quiz. Enjoy! For incorrect answers, click (+ show previous…
- 06.03.2009 - 1 CommentsA comprehensive framework for capitalizing on the growing market for Continuing Care Retirement…
thank you po s post :) d ko kc mkta ung dstnce s fire code.
ReplyDeleteHello. Is there a provision from the code regarding the distance between two fire exits? Thank you!
ReplyDelete